General
info ] [
Dimensions
] [
Wiring
] [
Installation
] [
Function
Blocks
] [
Programming on panel
] [
Online Store
]
General technical specifications
Item |
Basis |
Condition |
| Climate
environment |
| Ambient
temperature |
cold:
IEC68-2-1, hot: IEC68-2-2 |
|
Horizontal
installation Vertical installation |
|
0 ~ 55 C |
Storage/transportation |
|
-40 C ~ +70 C |
Relative humidity |
IEC68-2-30 |
5% ~ 95%,without
condensation |
Atmospheric
pressure |
|
795 ~ 1080kpa |
Pollutants |
IEC68-2-42
IEC68-2-43 |
H2Slcm3/m3, 4days
SO210cm3/m3, 4days |
Mechanical
environment |
Protection type |
|
IP20 |
Vibration 2 |
IEC68-2-6 |
10 ~ 57Hz (constant
amplitude 0.15mm)
57 ~ 150Hz
(constant acceleration 2g) |
Impact |
IEC68-2-27 |
18 impacts (semi sine
15g/11ms) |
Fall |
IEC68-2-31 |
falling height 50mm |
Freely falling body
(with package) |
IEC68-2-32 |
1m |
Electromagnetic
compatibility (EMC) |
Static discharge |
severe grade 3 |
8kv air discharge, 6kv
contact discharge |
Static discharge |
severe grade 3 |
8kv air discharge, 6kv
contact discharge |
Electromagnetic
field |
IEC801-3 |
field strength 10V/m |
Interference
suppression |
EN55011 |
limitation grade B group 1 |
Shock pulse |
IEC801-4
severe
grade 3 |
2.2kV for power line |
IEC/VDE safety
information |
Insulation
lntensity |
IEC1131 |
meeting the requirement |
|
|
SCM International, Inc.
Mailing Address:
SCM International, Inc.
2648 E. Workman Ave. suite 527
West Covina, CA 91791
USA
Fax: +1 (530)3256895
Corporate Headquarters POBOX:
SCM International, Inc.
POBOX 9793
Reno, NV . 89507
USA
SCMStore.com, license and Conditions of use |
SCM International, Inc.
license the user to use this application by the term of a session, only under the
following terms and conditions:
|
(c)
2008, SCM International, Inc. All right reserved.
|