RPR
|
Symbol |
Pin |
Description |
|

|
TRG |
Timer for ON time delay is
started via Input TRG (Trigger). |
|
R |
Timer for ON time delay is reset
to ON via Input R, and make Output Q
is 0 (The priority of R is higher than that
of TRG). |
|
T |
After TRG is triggered and the
time T elapses, the output is ON. |
|
Q |
After time delay T elapses, the
output is ON. |
Time
sequence frame:

Note
- If the status of Input TRG changes from 0 to 1,
the internal timer will be activated. Whentime T is up, Output Q becomes 1 and then the
input TRG coming again has no effect on output Q .Only when Input R becomes 1 again Output
Q and Timer T will be reset to 0.
- This function is applicable to the locations
where the time-delay ON and hold ON status are required.
- The assignment range for T is 0.01 - 99.99, and
the time units can be set respectively to hour (H), minute (M) and second (S). Its time
accuracy can reach 0.5 /00 Second.
|
|
|
|
|
|
|
|